Evaporative cooler size calculator
Evaporative coolers are sized by airflow (CFM or m³/h), not by tons or BTU like air conditioners. This gives a preliminary estimate, not professional sizing.
Assumptions (disclosed)
- Airflow = room volume × air changes per hour (÷ 60 for per-minute units). The 20–40 ACH range and method come from the US DOE Building America Solution Center, which notes that sizing "is not an exact science."[1]
- Relief area: 2 ft² of unrestricted opening per 1,000 CFM (≈ 0.11 m² per 1,000 m³/h) per DOE/PG&E guidance. Screens and louvres need more. An older DOE fact sheet gives 1–2 ft² per 1,000 CFM.[1][2]
- Cooling capacity is the sensible heat the supply air can absorb as it warms from outlet to indoor temperature: mass flow × specific heat × (indoor − outlet). It is a derived estimate shown for comparison with heat-load estimates. It is not an equipment rating.
- Manufacturer airflow ratings may be measured with less restriction than your installation (pads, ducts, grilles), so delivered airflow can be lower.
Worked example (from DOE)
A 2,000 ft² (186 m²) home with 8 ft (2.44 m) ceilings in a 20-ACH zone: 16,000 ft³ × 20 ÷ 60 = 5,333 CFM (≈ 9,060 m³/h).[1] Relief needed: about 10.7 ft² (1.0 m²). Both values are checked in our tests.
When to get professional help
Have a qualified installer verify the design for ducted systems, homes with large west-facing glass, poorly insulated roofs, multi-storey layouts, or any climate where the suitability check shows reduced performance. Duct design should follow a recognised method (DOE references ACCA Manual D).[1]
Sources
- U.S. DOE Building America Solution Center, "Evaporative Cooling Systems": ACH method, 20–40 ACH, worked example, relief area, Manual D.
- U.S. DOE / NREL, "Cooling Your Home with Fans and Ventilation" (DOE/GO-102001-1278): 1–2 ft² opening per 1,000 cfm; coolers rated 3,000–25,000 cfm.