Will an evaporative cooler work in your climate?

Evaporative coolers (also called swamp coolers, desert coolers or evaporative air coolers) can only cool air toward the wet-bulb temperature. Enter outdoor conditions to see how much cooling the air allows. For a fair assessment, use a typical hot afternoon or your local summer design condition, not a mild morning.

A normal thermometer or weather-app reading
1–100%, measured at the same time as the temperature
Sets air pressure (standard atmosphere)

What the numbers mean

Wet-bulb temperature
The lowest temperature air can reach by evaporating water into it. A perfect (100% effective) evaporative cooler would deliver air at this temperature.
Wet-bulb depression
Dry bulb minus wet bulb. This is the maximum possible temperature drop, so the bigger it is, the better evaporative cooling works. A real cooler achieves a fraction of it, set by its effectiveness.
Dew point
The temperature at which the air's moisture would condense. It changes slowly through a day, so a high dew point is an early warning that humid conditions are limiting your cooler.

How the verdict is decided

We use guidance from the US Department of Energy's Building America Solution Center: evaporative coolers work best where the summer design wet-bulb temperature is below about 21 °C (70 °F), and can still provide cooling up to about 23 °C (74 °F) with reduced performance. Above that, refrigerated air conditioning or a heat pump, which also removes moisture, is usually the better choice.[1]

Verdict bands (applied to the conditions you enter)
Wet bulbVerdict
≤ 21.1 °C (70 °F)Well suited
21.1–23.3 °C (70–74 °F)Works with reduced performance; consider indirect or two-stage
> 23.3 °C (74 °F)Poorly suited at these conditions

Worked example

The DOE source compares two US design days. At 42 °C (108 °F) dry bulb with a 21 °C (70 °F) wet bulb, typical of a desert city, the wet-bulb depression is 21 °C (38 °F) and evaporative cooling works very well. On a humid coastal design day of 33 °C (92 °F) with a 26 °C (79 °F) wet bulb, the depression is only 7 °C (13 °F).[1] Try both in the calculator.

Limitations, with no guarantees

Next steps

Estimate outlet air temperature · Size the airflow · Estimate water use · Compare running cost with AC

Sources

  1. U.S. Department of Energy, Building America Solution Center (PNNL), "Evaporative Cooling Systems": wet-bulb suitability thresholds, design-day examples, definition of wet-bulb depression.
  2. ASHRAE Handbook—Fundamentals (2017), Chapter 1 "Psychrometrics": moist-air equations used by the calculator.